E112—Overvoltage when running

the bus voltage is greater than 460v for 10ms  when running

Troubleshooting steps
Check whether the inlet voltage of control box is stable, if it’s within the specified range of 200V-250V
when standby, see what’s the voltage appear in U3 interface, then run the motor to see how much voltage rise while scram(usually around 410V), 【the inlet voltage multiplied by 1.41 = interface voltage】
if the voltage showed in U3 is wrong, using Isolation transformer with 80V to supply  power, then detect the voltage of control board’s bridge rectifier + anode to C4 negative terminal: inlet voltage multiplied by 1.41; C73 ends impedance: 12.5k or so; Two terminal voltage (means U9 foot 3# to foot 4#(safety line): 0.56V or so.
if the voltage showed in U3 is wrong, using Isolation transformer with 80V to supply  power, then see R143 resistance in main control board: 100Ω; C77 ends impedance: 3.8m or so; Two terminal voltage (means U9 foot 1# to foot 4#(safety line): 0.56V or so.
【share the maintenance picture of E111】